      HV self-regulating &  middle temperature electric heating cable

      SPECIFICATION:
      Self-regulating and save energy
      Voltage  220V/110V
      Max Using Length  120 m
      Max Heat tracing Temperature  110℃
      the most Suitable Temperature for heat tracing  80℃
      Outline Size 4.6×11.7 mm
      Local Cutting at random
      28 W/m、41W/m(10℃)
      Min. Bending Radius 30mm
      Fitting for Explosion-proof Area 1、2
      Temperature group T4
      Heat Output for Cable W/m
      A 14AWG Copper Bus Wires
      B Semiconductor Heating Core
      C Insaluting Jacket

      D Tinned Copper Braid

      E Overjacket(optional)
      Type
      Output Power
      45HV-2SJ
      45.0-0.37Tp
      30HV-2SJ
      30.3-0.24Tp
      Record:Tp is the pipe temperature
      Circuit  breaker selection(Unit: Meter)
      Cable
      Type
      Openning Temp.10℃
      Openning Temp.-10℃
      Openning Temp.-30℃
      15A
      20A
      30A
      40A
      15A
      20A
      30A
      40A
      15A
      20A
      30A
      40A
      50A
      30HV-2SJ
      43
      57
      86
      114
      39
      52
      78
      104
      36
      49
      72
      98
      120
      45HV-2SJ
      38
      51
      76
      100
      36
      48
      72
      96
      33
      44
      66
      88
      100
       Suggestion:  PLS using the thermal magnetic circuit breaker . For it can “nuisance trip” at low temperature.
      Type Number Nomenclature:

          
      ISO9001、Ex、ATEX、FM、EAC、CE、UL、WPQR(Comply With PED、ASME)    